Title: Performance and sustainability assessment of a geothermal district heating and cooling system through energy and exergy analyses
Authors: Ebru Hancioglu; Arif Hepbasli
Addresses: Geothermal Energy Research and Application Centre, Izmir Institute of Technology, 35430 Urla, Izmir, Turkey ' Department of Mechanical Engineering, Faculty of Engineering, Yasar University, 35100 Bornova, Izmir, Turkey
Abstract: A comprehensive thermodynamic analysis of a geothermal energy-supported heating and cooling system for a model building was presented in this study, employing energy, exergy, and sustainability evaluation methods. The heating and cooling systems achieved energy efficiencies of 0.81 and 0.47, respectively, while their corresponding exergy efficiencies were determined as 0.52 and 0.11. The coefficient of performance (COP) of the cooling system was calculated as 0.56. The results indicate that, in cooling mode, the condenser and absorber exhibit the greatest potential for performance and environmental improvement, whereas in heating mode, the heat exchanger (HE1) represents the principal component for enhancement.
Keywords: geothermal district; geothermal cooling; energy analysis; exergy analysis; sustainability analysis.
International Journal of Exergy, 2026 Vol.51 No.2, pp.79 - 95
Received: 19 Feb 2026
Accepted: 27 Mar 2026
Published online: 29 Sep 2026 *